| Sign In | Join Free | My enlightcorp.com |
|
Brand Name : Shelok
Certification : CE
Place of Origin : Shaanxi,China
MOQ : 1 piece
Price : USD+230-350+piece
Payment Terms : L/C, D/A, D/P, T/T, Western Union, MoneyGram
Supply Ability : 100+pieces+per month
Delivery Time : 3-15 work days
Packaging Details : Standard export carton packing or can be customized
Accuracy : ±0.1% URL ±0.2% URL
Output signal : 4~20mA, 4~20mA with HART
Application
Widely used in pharmaceutical, medical equipment, oil, gas, chemical, urban construction power, metallurgy, textile, aerospace, scientific research, leak detection, automation equipment and other fields.
Technical Data
| Measuring medium | liquid, gas |
| Measuring range | Range 3 0-1.3~7.5kPa |
| Range 4 0-6.2~37.4kPa | |
| Range 5 0-31~186.8kPa | |
| Range 6 0-117~690kPa | |
| Range 7 0-345~2068kPa | |
| Range 8 0-1170~6890kPa | |
| Range 9 0-3480~20680kPa | |
| Range 0 0-6890~41370kPa | |
| Accuracy | ±0.1% URL ±0.2% URL |
| Signal output | 4~20mA 4~20mA with HART |
| Supply voltage | 24VDC(12VDC~45VDC) Explosion-proof type:12~28VDC |
| Stability | ±0.1 URL in six months |
| Medium temperature | -40~+100°C |
| Storage temperature | -40~+100°C(without LCD display) -40~+70°C(with LCD display) |
| Operating temperature | -40~+85°C(without LCD display) -30~+60°C(with LCD display) |
| Ambient temperature | -0~-100% relative humidity |
| Temperature impact | ±(0.2%URL+0.18%inspection range)/56°C |
| Power supply effect | Less than 0.0059% / V of the output range |
| Load effect | No load is affected unless the supply voltage changes |
| Vibration effect | The vibration effect is ± 0.05% URL / g at 200 Hz in any axial direction. |
| EMI/RFI effect | Between 20 to 1000MHz;field strength up to 30V / M; the output drift less than ± 0.1% range; |
| Installation site effect | Maximum Zero drift is ± 0.25kPa; all zero drift can be corrected. |
| Zero point positive and negative migration | When zero is moving, the minimum range must be larger than or equal to - URL, the maximum range must be less than or equal to + URL. The calibration range must be greater than or equal to the minimum range. |
| Zero and range | Zero and range can be adjusted with the instrument range and zero button, or with the HART handhold remote adjustment. |
| Static pressure and over-pressure limit | Transmitter on any side plus 0 to 13.79MPa pressure will not cause damage. In the 0kPa to the transmitter range of the upper limit of the work to meet the performance requirements. |
| Damping time constant | The time constant is adjustable, incremented by 0.1 seconds, from minimum to 16.0 seconds. |
| Explosion-proof grade | Intrinsically safe: Exia II CT6 Flameproof: Exd II BT5 |
| Protection grade | IP65 |
Installation types


Electrical connections

Product details

|
|
Hart protocal SLK -3051 DP flange differential pressure transmitter Images |